Freon™ HP80 is an HCFC retrofit refrigerant for R-502 in existing low- and medium-temperature commercial refrigeration systems such as reach-in and walk-in freezers, as well as supermarket systems. Field experience has shown that no oil change is needed in many unitary and close-coupled systems.

General Property Information

SNo. Physical Physical Property Unit value
1 Molecular Weight, avg. g/mol 101.55
2 Boiling Point (1 atm) °C (°F) –49.2 (–56.5)
3 Freezing Point (1 atm) °C (°F N/A
4 Critical Temperature °C (°F) 75.5 (167.9)
5 Critical Pressure kPa (psia) 4135 (599.7)
6 Critical Density kg/m3 (lb/ft3) 541.7 (33.82)
7 Liquid Density at 25 °C (77 °F) kg/m3 (lb/ft3) 1151 (71.86)
8 Density, Saturated. Vapor at -15 °C (5 °F) kg/m3 (lb/ft3) 19.93 (1.24)
9 Specific Heat, Liquid at 25 °C (77 °F) kJ/kg·K (Btu/lb·°F) 1.3 (0.328)
10 Specific Heat, Vapor at 25 °C (77 °F) (1 atm) kJ/kg·K (Btu/lb·°F) 0.755 (0.181)
11 Vapor Pressure at 25 °C (77 °F) kPa (psia) 1337 (194.0
12 Heat of Vaporization at Boiling Point kJ/kg (Btu/lb) 194.0 (83.5)
13 Thermal Conductivity at 25 °C (77 °F)
Liquid Vapor (1 atm)
W/m·K (Btu/hr·ft·°F)
W/m·K (Btu/hr·ft·°F)
6.91E-2 (4.00E-2)
1.266E-2 (7.32E-3)
7
14 Viscosity at 25 °C (77 °F)
Liquid Vapor (1 atm)
Pa·s
Pa·s
1.38E-4
1.29E-5
15 Flammability Limit in Air (1 atm) vol% None
16 Ozone Depletion Potential (CFC-12 = 1.0) 0.02
17 Halocarbon Global Warming Potential (CFC-11 = 1.0) 0.63
18 TSCA Inventory Status Reported/Included? Yes
19 Inhalation Exposure Limit* ppm (8- and 12-hr TWA) 1000

Applications

Low- and medium-temperature commercial refrigeration equipment:

1. reach-in and walk-in freezers

2. supermarket system